Energy & carbon · FY25/26 · 18 sites
Energy
10.31 GWh
2.2% vs last year
Cost
£1,442,121
1.9% vs last year
electricity priced on contract
Emissions
1,983 tCO2e
2.1% vs last year
Identified savings
£75,344
across 11 quantified findings

Statutory reporting readiness

What stands between today and a clean SECR disclosure for FY25/26.

Total UK energy10,310,311 kWh
Above 40,000 kWh exemptionYes — disclosure required
Readings that are actual, not estimated98.72%
Meters with estimated reads2
Emission factor setdesnz-2025 (unverified)

Estimated reads are excluded from baselines and will be disclosed in the data-quality appendix: bath-milsom-elec, edinburgh-george-elec.

What needs attention

Ranked by severity, then by annual cost. Every figure links to the data behind it.

Unexpected consumption at Coventry Production Kitchen

Gas use runs about 13% above what Coventry Production Kitchen's electricity use implies on Tuesday and Thursday (207 days examined). Gas and electricity normally rise and fall together with covers served, so gas moving on its own suggests it is not producing output.

Check for equipment left running or a failed control.

CRITICALHigh confidence32.3 tCO2e/yrOpen evidence →q_aaf0d2a47d7e4245
£12,087per year

Step change in consumption at Manchester Piccadilly

Load rose by 261% on 2025-11-12 and has stayed there — about £10,689 a year. A persistent step usually means a setting changed or new equipment was installed.

Confirm what changed on or around 2025-11-12.

CRITICALHigh confidence8.9 tCO2e/yrOpen evidence →q_0c52349e110b04b0
£10,689per year

Cardiff Castle Street uses more than comparable sites

Cardiff Castle Street used 1.6 kWh per cover against a cafe_restaurant median of 1.2, a gap of 32%. The comparison is weather-adjusted and normalised by kWh per cover.

Compare plant, settings and opening hours against Birmingham Bullring.

CRITICALMedium confidence8.0 tCO2e/yrOpen evidence →q_05d6e701d02a3bef
£9,560per year

Coventry Production Kitchen may be on the wrong contract

25% of consumption falls in off-peak hours, but the site is on Fixed single rate. Re-pricing the same consumption under Day / night time-of-use would have cost £18,804 less over 2024-04-01 to 2026-03-31.

Ask your supplier to quote Day / night time-of-use at renewal. This compares the same consumption under both contracts; it assumes no change in usage.

HIGHHigh confidenceOpen evidence →q_44772edef37e1012
£18,804per year

Covent Garden may be on the wrong contract

8% of consumption falls in off-peak hours, but the site is on Half-hourly pass-through. Re-pricing the same consumption under Fixed single rate would have cost £9,149 less over 2024-04-01 to 2026-03-31.

Ask your supplier to quote Fixed single rate at renewal. This compares the same consumption under both contracts; it assumes no change in usage.

HIGHHigh confidenceOpen evidence →q_8b124a2f0e6852e7
£9,149per year

Head Office never fully powers down

Weekend load stays at 60% of a typical weekday. Sites of this type usually fall below 25%.

Identify what remains energised at weekends and whether it needs to be.

HIGHHigh confidence4.7 tCO2e/yrOpen evidence →q_4fe590293defe629
£5,657per year

Coventry Depot may be on the wrong contract

24% of consumption falls in off-peak hours, but the site is on Fixed single rate. Re-pricing the same consumption under Day / night time-of-use would have cost £3,981 less over 2024-04-01 to 2026-03-31.

Ask your supplier to quote Day / night time-of-use at renewal. This compares the same consumption under both contracts; it assumes no change in usage.

HIGHHigh confidenceOpen evidence →q_9d560ac5d9292d21
£3,981per year

Overnight baseload creeping up at Bristol Harbourside

The minimum overnight load has risen from 4.52 kW to 5.77 kW over 12.0 months — about £3,289 a year if it continues. A steady climb like this usually means equipment degrading rather than a change in trading.

Inspect refrigeration seals, door heaters and any always-on plant at Bristol Harbourside.

HIGHHigh confidence2.7 tCO2e/yrOpen evidence →q_2284391f40b6f802
£3,289per year

Plant starts 2.5 hours before Leeds Briggate opens

Load ramps up at 05:30 but the site opens at 08:00, costing about £1,049 a year.

Trim the start time toward 07:30 and check whether the space still reaches temperature in time.

MEDIUMMedium confidence0.9 tCO2e/yrOpen evidence →q_7513928dc1785fdf
£1,049per year

Estimated readings at Bath Milsom Street

6% of readings for 2026-01-12 to 2026-02-22 are estimated rather than actual. These are excluded from baselines and flagged in the statutory report.

Ask the supplier for actual reads covering 2026-01-12 to 2026-02-22.

MEDIUMHigh confidenceOpen evidence →q_38321a28c74e210d
no cost impact

Estimated readings at Edinburgh George Street

6% of readings for 2026-01-12 to 2026-02-22 are estimated rather than actual. These are excluded from baselines and flagged in the statutory report.

Ask the supplier for actual reads covering 2026-01-12 to 2026-02-22.

MEDIUMHigh confidenceOpen evidence →q_908314189317185e
no cost impact

Fuel efficiency falling for van-07

van-07 averaged 26.4 mpg over 2024-04-01 to 2026-03-31, down 10% from 29.4 mpg.

Book a service check — tyre pressures, filters and driving pattern.

LOWMedium confidence0.9 tCO2e/yrOpen evidence →q_f28129ffebf340af
£547per year

Unexpected consumption at Coventry Production Kitchen

Consumption on 2025-02-18 was 21,709 kWh against an expected 16,747 kWh after adjusting for weather and trading hours.

Check for equipment left running or a failed control.

LOWHigh confidence1.4 tCO2e/yrOpen evidence →q_9948f99dbd031462
£533per year

What we could not check

5 detector runs were skipped because the data does not support them. Absence of a finding in these areas is not evidence of absence.